novaPro32 Routel
Important information concerning Routel functions
32
7000991003 Q2
Sauter Systems
7
7.2 Changes in the system groups of the
EP server and HDB server groups
For installations with a low number of islands, we recommend that, after each
modification to the configuration of the EP server and/or the HDB server, the system be
ended with a ‘cold’ stop and then re-started with a ‘cold’ start.
For installations with a high number of islands, proceed as follows:-
Using the ‘De-activate’ button from the ‘Connections’ dialog box, de-activate
the addresses of the island(s) affected by the changes.
The changes are then made in the EP server and/or in the HDB server.
Close the novaPro32 program with a ‘cold’ stop.
There are two ways of re-starting:-
Either with a ‘warm’ start and by manually activating each of the islands that
have been changed (using the ‘Activate’ button from the ‘Connections’ dialog
box).
Or with an automatic ‘cold’ start of all connections.
The above-mentioned functions are carried out in the following window:-