1.3 Introduction
Remote Supervision, Routel:
Remote Supervision: The PC and AS island are linked via modems. Alarms and limit
violations are messaged from the island towards the PC.
The activation (subscription for the spontaneous upload) of Routel addresses on the AS
is on the Routel dedicated DW34 and not on the standard DW 35 (from V4.0SR1-
Routel!).
However, in installations with Routel and non-Routel islands, the activation of addresses
on the non Routel islands is on DW35. Also when accessing a Routel island from the
PC (Remote access!) the activation of these addresses (Pictures, address lists,
Trends) is on DW35 and not on DW34. DW34 is used exclusively for the activation of
addresses that have to be spontaneously transmitted by the Routel towards the PC (EP
addresses).
Features Remote Supervision
1. Local Operation PC on the Routel island
An unlimited number of Operation PC (256) may be connected to a Routel island, or
may access a Routel island in Remote Access (Router) mode, without having an
influence on the Routel Operations.
2. Up to four Routel (Remote Supervision PC) per AS-Network
Up to four Routel, each serving its own Remote Supervision PC, can be connected
to a Routel island. Each of the Remote Supervision PCs can activate its own set of
addresses for spontaneous messaging (DW34).
3. No garbage collection for the Routel addresses
There is no garbage collection for the Routel addresses (DW34). Consequently,
there is no daily telephone call to re-activate these addresses.
4. Cold/warm stop/start
EY3600 novaPro32 can be stopped and re-launched either with, or without the de-
activation/re-activation of the addresses concerned (selectable).
When using the warm stop/start option of novaPro32, the lengthy calling of each
island during the stop and start procedure is omitted.
On the other hand, the data base of the current alarms on the PC is lost and not
refreshed when warm starting. This leads to no alarms being displayed in the alarm
list thereafter. Therefore, it's possible to also make a cold start after the system had
been stopped with a warm stop.
After a warm start, however, the data base of the current alarms is also refreshed at
the next following messaging of an event from the island and the alarms of this
island are displayed in the alarm list thereafter.